Limits of Estimating AI Inference Electricity Use From Query Counts as Agents Add Internal Processing

The average that determines one typical request and total electricity use
How much electricity does AI use? For text generation in the Gemini app in May 2025, Google reported median electricity use of 0.24Wh (watt-hours) per request. Its calculation included not only the equipment used for AI computation but also CPUs, RAM, idle equipment, and data-center overhead.
Multiplying the number of user queries by 0.24Wh may appear to yield annual electricity use. The problem is the difference between the median and the arithmetic mean. The median is the middle value after requests are sorted by electricity use. Calculating a total by multiplying by the number of requests requires the arithmetic mean across all requests being aggregated.
On November 24, 2026 (UTC), two researchers at Australia's Griffith University posted the preprint Typical-query energy figures mislead institutional AI electricity demand.
The researchers built SULLEE, a model for estimating inference electricity use by large language models (LLMs). It estimates the electricity used by individual inference requests from factors including input and output length, model design, GPU performance, and data-center overhead, then aggregates them at the organizational level while accounting for differences in user counts and workload types.
Figure 3 of the paper shows the distribution of inference electricity use across 50,000 simulated requests. Under the assumed workload mix, the median per inference request was 0.297Wh and the arithmetic mean was 0.797Wh. The mean was about 2.7 times the median, pulled upward by a small number of intensive requests.
Estimated AI inference electricity use by workload (Wh/request)
| Workload | Median | Arithmetic mean |
|---|---|---|
| General chat | 0.140 | 0.261 |
| Long-document processing | 0.169 | 0.319 |
| Code completion | 0.208 | 0.458 |
| Answers using retrieved information | 0.462 | 0.859 |
| Answers with extended reasoning | 0.852 | 1.601 |
| Deep problem solving | 2.424 | 5.464 |
| All requests (reference mix) | 0.297 | 0.797 |
A few intensive requests can have a large effect
SULLEE estimated mean electricity use of 0.261Wh for general chat, 0.319Wh for long-document processing, and 0.458Wh for code completion. It rose to 0.859Wh for retrieval-augmented generation (RAG), which searches external information for use in an answer, and 1.601Wh for responses involving extended reasoning.
Deep problem solving required a mean of 5.464Wh, about 21 times the figure for general chat. The top 10% of requests by electricity use accounted for 57.8% of total estimated electricity use. Even the top 1% accounted for 22.6%.
An LLM divides text into processing units called tokens, reads the input, and then generates output. Inference electricity use depends not only on the number of tokens processed but also on computation, data transfers to and from memory, and the efficiency of handling multiple requests concurrently.
A Microsoft Research study from April 2026 also estimated that optimized inference at large service scale uses a median of less than 1Wh. It showed that long reasoning and agentic processing could greatly increase electricity use by generating more tokens and reducing the number of requests that can be processed concurrently.
Even in a service dominated by light requests, a small number of intensive requests can heavily influence total electricity use. Required electricity changes with usage patterns even when the number of requests stays constant.
One query can generate multiple inference requests
Imagine asking an AI agent to conduct research. The user sends one instruction. The AI creates a work plan, searches for information, reads the results, and decides what to investigate next. It may call the model at each stage.
Documents found through search and results from earlier processing may also be added to the next model call's input. More calls and larger inputs combine to change the internal workload generated by each user instruction.
Indeed, a separate study on agentic coding work, revised in October 2026, reported that input rather than output was the major source of token consumption. This should be distinguished from measurements of electricity use, but it shows the difficulty of judging the total scale of processing from only the final answer displayed on screen.
SULLEE distinguishes between user messages and additional model calls derived from them. It also includes input tokens added through search results and other sources in its estimates.
Annual electricity use modeled for a university with 20,000 students
The researchers modeled annual inference electricity use under three conditions for an Australian university with about 20,000 students, accounting for use by students, faculty, and staff. Mean annual use was estimated at 17.3MWh (megawatt-hours) for observed use in 2026, driven mainly by voluntary individual adoption; 53.9MWh for a 2026 scenario in which the university supports adoption through licenses and training; and 287.4MWh for advanced workplace integration in 2030.
AI inference estimates for an Australian university with 20,000 students
| Usage scenario | 2026 Primarily voluntary individual use | 2026 Institution-supported adoption | 2030 Advanced integration |
|---|---|---|---|
| Annual messages and model calls (mean) | |||
| Messages (10,000s) | 1717 | 3205 | 6463 |
| Calls (10,000s) | 1938 | 4415 | 14015 |
| Calls per message | 1.13 | 1.38 | 2.17 |
| Annual inference electricity use (MWh), 2026 baseline efficiency | |||
| Simple estimate Messages × 0.297Wh | 5.1 | 9.5 | 19.2 |
| Detailed estimate | 17.3 | 53.9 | 287.4 |
| Central 90% range | 3.1~47.1 | 9.8~144.8 | 41.5~830.7 |
| Detailed ÷ simple | 3.4× | 5.7× | 15.0× |
| Estimate from all calls × 0.797Wh | |||
| Share of detailed estimate | 89% | 65% | 39% |
The ratio of total model calls to user-submitted messages also changes. Per message, the study estimated about 1.13 calls under observed use, 1.38 under institution-supported adoption, and 2.17 under advanced integration.
The observed-use scenario estimated a mean of 17.17 million messages per year. Multiplying that by the reference scenario's median of 0.297Wh produces about 5.1MWh, roughly 70% less electricity than the detailed estimate of 17.3MWh.
For the advanced-integration scenario in 2030, the mean annual message count was estimated at 64.63 million. The simple estimate based on the median was about 19.2MWh, while the detailed estimate of 287.4MWh was about 15 times higher.
Differences remained even when the reference scenario's arithmetic mean replaced the median and the total number of model calls replaced the number of user messages. Relative to the detailed estimates, those calculations reached about 89% under observed use, 65% under institution-supported adoption, and 39% under advanced integration. The effective mean electricity use in each scenario also changes with the mix of workload types.
Considering efficiency gains together with growth in use
In the 2030 advanced-integration scenario, agent-related processing accounted for about 78% of annual inference electricity use. Processing the inputs added through search results and related work alone accounted for about 43% of the total.
The 287.4MWh estimate uses inference efficiency based on 2026. Holding the 2030 workload constant, the researchers calculated that a uniform improvement of about 5.3 times in inference energy efficiency would reduce annual electricity use to roughly the level of the 2026 institution-supported adoption scenario.
Technical improvements can reduce electricity consumption. How organization-wide use changes depends on both growth in use and efficiency improvements.
The 2030 advanced-integration scenario has a wide uncertainty range of 41.5–830.7MWh, excluding the bottom and top 5% of model outputs. Public information about commercial AI model design and operation is limited, and future usage is also uncertain. The researchers assigned ranges of assumptions to each factor.
These are model-based estimates using public specifications, benchmarks, and other sources and should be distinguished from electricity measured directly at commercial AI data centers. The estimates cover the operational electricity used for LLM inference services. The environmental effects of model training and development, semiconductor manufacturing, and the electricity directly used by external search services and tools require separate assessment. Annual electricity estimates also cannot directly determine a data center's peak power demand.
Measuring the work an organization delegates to AI
In Japan, Nagoya Institute of Technology announced on January 21, 2026, that it had introduced ChatGPT Edu for all full-time faculty and staff as a generative AI service for educational institutions. At the time of the announcement, it was also considering providing generative AI to master's students entering from April 2027.
When a university or company adopts AI, estimating what work will be delegated to it, in addition to the number of licensed users, also informs electricity-use assessments. This is particularly important as research, development, and other work involving multiple inference calls expands.
The Griffith University researchers propose disclosing information including the model and use case, input and output tokens, the distinction between means and medians, and how much facility electricity is included. They also emphasize comparing electricity use alongside performance and price and increasing useful outcomes per unit of electricity consumed.
Avoiding complex work solely because of electricity use could undermine the purpose of adopting AI. Conversely, repeatedly applying more inference than necessary to simple tasks can increase electricity use without producing more useful results. The study of token consumption in coding work showed that using more tokens does not necessarily improve accuracy.
Improving energy efficiency while making use of AI's capabilities also requires understanding which requests consumed electricity. To know the outcomes produced per unit of electricity, organizations need visibility into how many times a model ran during a task and what it processed.